Chuango SMK-500 User Manual

Browse online or download User Manual for Smoke detectors Chuango SMK-500. Chuango SMK-500 smoke detector

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
User Manual
Smoke Detector
Ideal for All Areas
Our photoelectric smoke detector is designed to sense smoke that comes into
the detector chamber. It does not sense gas, heat, or flame. This smoke
detector is designed to give early warning of developing fires by giving off the
alarm sounds from its built-in alarm horn. It can provide precious time for you
and your family to escape before fire spreads. However, the smoke detector
makes such pre-warning of fire accident possible, only if the detector is
located, installed, and maintained properly as described in this User's Manual.
WARNING: This smoke detector is designed for use in a single residential unit
only, which means that it should be used inside a single family home or
apartment. It is not meant to be used in lobbies, hallways, basements, or
another apartment in multi-family buildings, unless there are already working
detectors in each family unit. Smoke detectors, placed in common areas
outside the individual living unit, such as on porches or in hallways, may not
provide early warning to residents. In multi-family buildings, each family living
unit should set up its own detectors.
WARNING: This detector is not meant to be used in non-residential buildings,
warehouses, industrial or commercial buildings, and special purpose non-
residential buildings require special fire detection and alarm systems. This
detector alone is not a suitable substitute for complete fire detection systems
for places where many people live or work, such as hotels or motels. The same
is true of dormitories, hospitals, nursing homes or group homes of any kind,
even if they were once single family homes. Please refer NFPA 101, the Life
Safety Code, NFPA71, 72A, 72B, 72C, 72D, and 72E for smoke detector
requirements for fire protection in buildings not defined as “households”.
Introduction
Smoke detectors should be installed in accordance with the NFPA Standard 74
(National Fire Protection Association, Battery march Park, Quincy, MA 02169).
For complete coverage in residential units, smoke detectors should be
installed in all rooms, halls, storage areas, basements, and attics in each family
living unit. Minimum coverage is one detector on each floor and one in each
sleeping area and attics in each family living unit.
Locations to Install Your Smoke Detectors
Install basement detectors at the bottom of the basement stairwell.
Install second-floor detectors at the top of the first-to-second floor stairwell.
Be sure no door or other obstruction blocks the path of smoke to the detector.
Install additional detectors in your living room, dining room, family room, attic,
utility and storage rooms.
Install smoke detectors as close to the center of the ceiling as possible. If this is
not practical, put the detector on the ceiling, no closer than 4 inches (10 cm)
from any wall or corner, as shown in Figure 4.
If ceiling mounting is not possible and wall mounting is permitted by your local
and state codes, put wall-mounted detectors between 4 and 6 inches (10 ~ 15
cm) from the ceiling, also see Figure 4.
If some of your rooms have sloped, peaked, or gabled ceilings, try to mount
detectors 3 feet (0.9 meter) measured horizontally from the highest point of the
ceiling as shown in Figure 5.
Here, we have useful tips for you:
Install a smoke detector in the hallway outside every separate
bedroom area, as shown in Figure 1. Two detectors are required in
homes with two bedroom areas, as shown in Figure 2.
Install a smoke detector on every floor of a multi-floor home or
apartment, as shown in Figure 3.
Install a minimum of two detectors in any household.
Install a smoke detector inside every bedroom.
Install smoke detectors at both ends of a bedroom hallway if the
hallway is more than 40 feet (12 meters) long.
Install a smoke detector inside every room where one sleeps with
the door partly or completely closed, since smoke could be blocked
by the closed door and a hallway alarm may not wake up the
sleeper if the door is closed.
DINNG ROOM
BED ROOM
KITCHEN
BED
ROOM
BED
ROOM
LIVING ROOM
SMOKE DETECTORS FOR MINIMUM SECURITY
SMOKE DETECTORS FOR MORE SECURITY
Figure 1: locations for placing smoke detectors for single residence with only
one sleeping area
Figure 2: locations for placing smoke detectors for single-floor residence with
more than one sleeping area
BEDROOM
BEDROOM BEDROOM
GROUND
FLOOR
KITCHEN
GARAGE
BASEMENT
SMOKE DETECTORS FOR MINIMUM SECURITY
Figure 3: locations for placing smoke detectors for a multi-floor residence
SMOKE DETECTORS FOR MINIMUM SECURITY
SMOKE DETECTORS FOR MORE SECURITY
FAMILY ROOM KITCHEN
BED
ROOM
BED
ROOM
LIVING ROOM
BED
ROOM
BED ROOM
BEST LOCATION
ACCEPTABLE
LOCATION
CEILING
4in
(10cm)
CENTER OF
CEILING
NEVER
HERE
4in
(10cm)
Minimum
6in(15cm)
Maximum
BEDROOM
AIR RETURN
AIR ENTRY
STOVE
KITCHEN
BEDROOM
LIVING ROOM
CORRECT LOCATION
INCORRECT LOCATION
DETECTOR
9 FEET
HORIZONTAL DISTANCE
FROM PEAK
Figure 4: recommended best and acceptable locations to mount smoke
detectors
Figure 5: recommended locations to mount smoke detectors in rooms with
sloped, gabled, or peaked ceiling
“Early warning fire detection is best achieved by the installation of fire
detection equipment in all rooms and areas of the household as follows: (1) A
smoke detector installed in each separate sleeping area (in the vicinity, but
outside of the bedrooms), and (2) Heat or smoke detectors in the living
rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms,
closets, utility and, storage rooms, basements and attached garages.
For your information, NFPA Standard 74, Section 2-4 reads as follows:
“2-4.1.1 Smoke detectors shall be installed outside of each separate sleeping
area in the immediate vicinity of the bedrooms and on each additional story
of the family living unit including basements and excluding crawl spaces and
unfinished attics.
The provisions of 2-4.1.1 represent the minimum number of detectors
required by this standard. It is recommended that the householder considers
the use of additional smoke detectors for increased protection for those areas
separated by a door from the areas protected by the required smoke
detectors under 2-4.1.1 above. The recommended additional areas are living
room, dining room, bedroom(s), kitchen, attic (finished or unfinished), furnace
rooms, utility room, basement, integral or attached garage, and hallways not
included in 2-4.1.1 above. However, the use of additional detectors remains
the option of the householder.” We recommend complete coverage and use
of additional smoke detectors.
CAUTION (As required by the California State Fire Marshall)
Locations not to Install Your Smoke Detectors
Nuisance alarms take place when smoke detectors are installed where they
will not work properly. To avoid nuisance alarms, do not install smoke
detectors in the following situations:
Combustion particles are the by-products of something that is burning. Thus,
in or near areas where combustion particles are present you do not install the
smoke detectors to avoid nuisance alarms, such as kitchens with few windows
or poor ventilation, garages where there may be vehicle exhaust, near
furnaces, hot water heaters, and space heaters.
Do not install smoke detectors less than 20 feet (6 meters) away from places
where combustion particles are normally present, like kitchens. If a 20-foot
distance is not possible, e.g. in a mobile home, try to install the detector as far
away from the combustion particles as possible, preferably on the wall. To
prevent nuisance alarms, provide good ventilation in such places.
IMPORTANT: For any reason, do not disable the detector to avoid nuisance
alarms.
When air streams passing by kitchens, the way how a detector can sense
combustion particles in normal air-flow paths is graphically shown in Figure 6,
which indicates the correct and incorrect smoke detector locations
concerning this problem.
Figure 6: recommended smoke detector locations to avoid air streams with
combustion particles
WARNING: Never remove batteries to stop a nuisance alarm. Open a window
or fan the air around the detector to get rid of the smoke. The alarm will turn
itself off when the smoke is gone. If nuisance alarms persist, attempt to clean
the detector as described in this User s Manual.
WARNING: Do not stand close to the detector when the alarm is sounding.
The alarm is loud in order to wake you in an emergency. Too much exposure
to the horn at close range may be harmful to your hearing.
In damp or very humid areas, or near bathrooms with showers. Moisture in
humid air can enter the sensing chamber, then turns into droplets upon
cooling, which can cause nuisance alarms. Install smoke detectors at least 10
feet (3 meters) away from bathrooms.
In ver y cold or very hot areas, including unheated buildings or outdoor
rooms. If the temperature goes above or below the operating range of smoke
detector, it will not work properly. The operating temperature range for your
smoke detector is 40 F to 100 F (4 C to 38 C).
In ver y dusty or dirty areas, dirt and dust can build up on the detector s
sensing chamber, to make it over sensitive. Additionally, dust or dirt can block
openings to the sensing chamber and keep the detector near fresh air vents
or ver y drafty areas like air conditioners, heaters or fans, fresh air vents and
drafts can drive smoke away from smoke detectors.
Dead air spaces are often at the top of a peaked roof, or in the corners
between ceilings and walls. Dead air may prevent smoke from reaching a
detector. See Figures 4 and 5 for recommended mounting locations.
In insect-infested areas. If insects enter a detectors sensing chamber, they
may cause a nuisance alarm. Where bugs are a problem, get rid of them
before putting up a detector.
Near fluorescent lights, electrical “noise” from fluorescent lights may cause
nuisance alarms. Install smoke detectors at least 5 feet (1.5 meters) from such
lights.
BATH
SMK-500 (Wireless)
SMK-500D (Independent)
Page view 0
1 2 3

Summary of Contents

Page 1 - one sleeping area

User ManualSmoke DetectorIdeal for All AreasOur photoelectric smoke detector is designed to sense smoke that comes into the detector chamber. It does

Page 2

CAUTION: This smoke detector comes with cover latches that will prevent the smoke detector cover from closing if battery is not installed. This tells

Page 3 - 角线折法,顺序为绿、蓝。保持产品名称在最上面

产品型号SMK-500林寿说明书设 计印刷尺寸工 艺部件名称材 料版 本成品尺寸105X95mm80克书写纸折页420X285mm注:双色、双面印刷角线折法,顺序为绿、蓝。保持产品名称在最上面Ver: SMK-500-EN-1405-V2.0

Comments to this Manuals

No comments